Module fan cooling tower ÌÂÃ-27.44. “VORTAX”
|
COOLING TOWER ÌÂÃ-27.44. “VORTAX”
TECHNICAL SPECIFICATIONS OF COOLING TOWER

|
NAME OF THE PARAMENTER |
MEASURING UNIT |
VALUE |
|
NAME OF THE COOLING UNIT |
|
ÌÂÃ-27.44.
“VORTAX” |
2ÌÂÃ-27.44. “VORTAX” |
|
OPERATION CONDITIONS |
|
PERFORMANCE RANGE OF THE COOLNG TOWER ON WATER
|
M3/HOUR |
45-85 |
45-170 |
|
NOMINAL PERFORMANCE RANGE OF THE COOLNG TOWER ON WATER
|
Ì3/ HOUR |
60-75 |
120-150 |
|
MAXIMUM TEMPERATURE OF HEATED WATER ON THE INPUT OF THE COOLING TOWER
|
°Ñ |
NOT MORE THAN 65 |
NOT MORE THAN 65 |
|
DROPLET ENTRAINMENT
|
% |
0,007 |
0,007 |
|
EVAPORATION LOSSES AT DT =10°C AND AIR TEMTERATURE 28-30 °Ñ
|
% |
1,5 |
1,5 |
|
PRESSURE IN A DISCHARGE PIPE AT THE BASE OF THE COOLING TOWER |
ÌCE |
4÷5 |
4÷5 |
|
CONSTRUCTION OF COOLING TOWER |
|
TYPE OF THE COOLING TOWER |
|
CONTER-FLOW EXHAUST |
|
NUMBER OF SECTIONS |
PIECE |
1 |
2 |
|
DIMENTIONS OF COOLING TOWER |
Ì |
2,40 Õ 2,40 |
4,80 Õ 2,40 |
|
DIMENTIONS OF SECTION |
Ì |
2,40 Õ 2,40 |
2,40 Õ 2,40 |
|
HEIGHT OF WATER INLET WITHOUT PALLET / TAKING INTO ACCOUNT THE PALLET
|
Ì |
2,265/2,685 |
2,265/2,685 |
|
OVERALL HEIGHT OF COOLING TOWER
INLET WITHOUT PALLET / TAKING INTO ACCOUNT THE PALLET
|
Ì |
3,486/3,906 |
3,486/3,906 |
|
NUMBER OF CLAMPING SHOULDERS OF WATER INLET |
ÌÌ |
1X 150 |
2 X 150 |
|
IRRIGATION AREA
|
Ì2 |
5,76 |
11,52 |
|
FAN INSTALLATION |
|
NUMBER OF FANS |
PIECE. |
1 |
2 |
|
INSTALLATION TYPE |
|
AXIAL |
|
CONNECTION TYPE OF MOTOR AND FAN |
|
DIRECT DRIVE |
|
FAN DIAMETER |
ÌÌ |
1500 |
1500 |
|
ROTATION RATE |
R/MIN. |
750 |
750 |
|
NOMINAL POWER OF ELECTROMOTOR |
kW |
1 Õ 7,5 |
2 Õ 7,5 |
|
ELECTROMOTOR PARAMETERS |
|
380/3/50 |
380/3/50 |
|
ELECTROMOTOR PROTECTION |
|
IP55, F |
IP55, F |
|
 |