COOLING TOWER ÃÌÂ 60, - 100 “SUPER”

COOLING TOWER ÃÌÂ 60, -100 “SUPER”

 

Purpose, operation principles

The compact fan cooling towers ÃÌÂ -60, -100 “SUPER” are the new improved version of the cooling towers with a maximum flow rate of circulating water of 60 and 100 m3/hour, which have several advantages compared to the previous model (the  cooling towers  ÃÌÂ-60Í and ÃÌÂ-100Í):
- compact dimensions of the cooling tower (reduced length of the cooling tower due to the absence of the extended diffuser)
- fan installation is placed inside the cooling tower, which completely eliminates the possibility of freezing of the fan impeller;
- more powerful motor of  fan installation;
- improved cell water catcher from profiled polypropylene plates;
- improved design of nozzles – improved spray pattern;
- modified collector of water distribution system, which simplifies inspection and cleaning of the irrigator.
Also like the previous model, the cooling tower  ÃÌÂ-60 and-100 “SUPER” consists of 2 mounting blocks providing easier transportation and installation, as well as free access to the nozzles,  irrigator,  water catcher .
All of the steel constructions of cooling towers are made of steel St.3. and covered with a special multi-component anti-corrosion coating.

 

 Complement of cooling towers of  ÃÌÂ-60 and-100 “SUPER” series  includes:


• combined irrigator of gofer PVC sheets and dimensional lattice elements. Combined irrigator has a high cooling capacity;


• cell water catcher from profiled polypropylene plates;


• plastic nozzle;


• axial fan.

TECHNICAL SPECIFICATIONS OF COOLING TOWERS OF  ÃÌÂ-60 AND-100 “SUPER” SERIES 

NAME OF THE PARAMETER
MEASURING UNIT 
ÃÌÂ-60
“SUPER”
ÃÌÂ- 100 “SUPER”
OPERATION CONDITIONS
Type of cooling tower
 
conter -flow exhaust
Type of irrigator
 
slick
Length of cooling tower
MM
2015
2685
Width of cooling tower
MM
2015
2265
Height of water input
MM
2645
3066
Total height of cooling tower
MM
2960
3320
Type  of connection between motor and fan
direct
Fan diameter
MM
1000
1000
Electromotor parameters
V/Hz/F
380 /50 /3
Nominal power of electromotor
kW
3,0
7,5
Electromotor protection
IP54
Number of clamping shoulders of water inlet
MM
100
1 X 150
Mass of cooling tower dry / working
kg
1300/2600
1800/4100
Performance on water
Ì3/ HOUR
40 ÷ 60
50 ÷ 100
Temperature of water on the input of the cooling tower
°Ñ
not more than 65
Temperature difference
°Ñ
5 ÷ 15
Temperature load DT = 5÷15 °Ñ and Qmax
kW
350 ÷ 1050*
580 ÷ 1750*
Droplet entrainment
%
0,0005
Pressure in water distribution system
ÌCE
3÷ 5
Volume  of receiving tank.
M3
1,2
2,2

* - the estimated value, depending on the flow rate of circulating water Q (m2/hour) and temperature difference Δt
(°Ñ), air wet bulb   t (°C) and the temperature of the cooled water t2(°Ñ).

 

G Analytics
ñàéò ñîçäàí êîìïàíèåé