Cooling tower with closed cooling water ÃÇÊ-11

COOLING TOWER
WITH CLOSED COOLING WATER ÃÇÊ 11

Cooling towers are produced in accordance with technical specifications ÒÓ Ó 29.2-20054481-003-2007 and are protected with the patent, the trademark.

The fan cooling tower with closed cooling water is designed for cooling of fluid (prepared (distilled) water, oil, hydroalcoholic solutions, etc.) circulating in a closed circuit without breaking the flow and the loss of working pressure.

The cooling tower with closed cooling water has two independent circuits: “technical equipment – cooling tower heat exchanger" and “water collecting pallet of the cooling tower – water distribution system of cooling tower”, which prevents the evaporation and mixing of the cooled fluid with the cooling circulating water.

Project data ÃÇÊ-11
Performance on heat exchanger Q, m3/hour (circuit “technical equipment – cooling tower heat exchanger") 40÷60
Performance on irrigation water Q, m3/hour (circuit “water collecting pallet of the cooling tower – water distribution system of cooling tower”) 50÷80
Volume of water collecting pallet, m3 2,3
Loss of irrigating water with droplet entrainment, % Not more than 0,007
Type of fan Axial, direct drive
Number of fan installations, pcs. 1
Fan diameter, mm 1240
Consumed power of fan electromotor, kW (5,5÷7,5)õ1 pcs.
Parameters of fan electromotor, V/Hz/F 380/50/3
Noise level on distance of 10m,dB Not more than 70
Number of circulating pumps, pcs. 1
Consumed power of pump electromotor, kW (2,0÷4,0)õ1 pcs.
Type of cooling tower Counter-flow
Weight of cooling tower dry/operating, kg 3000/4500
Production material:
- housing fiberglass
- heat exchanger copper
-water distribution system PVC
Cooling tower with closed cooling water ÃÇÊ-11

G Analytics