COOLER ÃÌÂ – 10Ï

COOLER  ÃÌÂ – 10Ï

Compact fan cross flowed cooling tower ÃÌÂ-10Ï is manufactured in accordance with ÒÓ (TECHNICAL SPECIFICATIONS) Ó 29.2-20054481-003-2007, is protected by patent, trade mark.

The cooling tower is designed to cool the water in the circulating water supply systems of compressor stations, cooling installations, air conditioning systems and other heat exchange equipment in which the heat must be removed by means of cooling water.

The latest developments of the global level are applied in the cooling tower of production “BROTEP”. That ensures efficient cooling of circulating water under the most adverse environmental conditions.

Sr. No Name of the parameter Value of the parameter
1
The hydraulic load (water flow), m3 / hour
 
 
- minimal
5
 
- nominal
8
 
- maximal
10
2
Water pressure at the cooling tower input, MCE (kgf/cm2)
2 ÷ 6 (0,2 ÷ 0,6)
3
Water temperature difference, °C
5 ÷ 15
4
Thermal load, Megacalories/h (kW)
25 ÷ 150 (29 ÷ 174)
5
Droplet Entrainment, %
No more than 0.01
6
The type and number of spray tube jets
ÑÒ-20 õ 12 – 6 pcs
7
Axial Fan  06-300
N 6,3
8
Electromotor Power, êW
0,75
9
The noise level at a distance of 10 m, Db
No more than 70
10
Dimension Sizes (length x wide x height), mm
1850 x 850 x 1725
11
Allowable temperature of the water at the cooling tower input, °Ñ
No more than  65
12
Capacity of the receiving tank, m³
0,35
13
Branch pipe of water supply ( Dó 1 ), mm
50
14
Overflow ( Dó 2), mm
20
15
Spill pipe ( Dó 3 ), mm
65
16
Weight without water / with water, kg
320 / 720

The principle of operation

The heated water is supplied to the nozzles, which spray it evenly over the surface of the irrigator, through pipes of water distribution system.

Draining on corrugated plate of irrigator in the form of slick, the water is cooled by cross air flow that is created by a fan, and is collected in the receiving tank.

Drops of water, which are carried away by the flow of air, are collected by water catchers.

Differential characteristics

  • The polymeric PVC irrigator has a high specific surface area (up to 300 m2/m3), provides the intensive cooling of water at a low aerodynamic drag, does not sustain combustion, is not clogged, resistant to low temperatures, the life service - up to 15 years.
  • The efficient water catcher of PVC profile elements virtually eliminates droplet entrainment of water. Specially designed construction of water catchers minimizes the aerodynamic drag, which improves cooling efficiency. Water catcher’s material does not sustain combustion, resistant to low temperatures.
  • The axial fan designed specifically for use in cooling towers. Thanks to the special design of the cooling tower, the fan is not exposed to the harmful effects of hot and humid air.
  • Specially designed cooling tower provides easy access to the nozzles, irrigators, water catchers. The internal and external metal surface of cooling  tower are treated  with anticorrosive coating based on organic resins and natural oils with special additives

 