COOLING TOWERS ÁÂÃ-80 “TURBO”
/ÁÂÃ-1000 “TURBO”- name of the cooling tower up to 2011/
Block fan cooling towers ÁÂÃ-80 “TURBO” are protected with patent and trade mark.
Efficient cooling of circulating water is guaranteed even under the most unfavorable external conditions due to the usage of the latest developments of world level in cooling towers of “BROTEP” production.
Name of parameter |
Measuring unit |
Value |
Operation conditions |
Performance on water |
m3/hour |
500-1000 |
Type of irrigator |
|
Combined(Film + net layer) |
Temperature of incoming water |
°Ñ |
Not more than 65 |
Temperature of cooled water |
°Ñ |
t* + (4÷6) |
Temperature difference, Δt |
°Ñ |
5÷20 |
Thermal load at Δt=10°Ñ |
kW |
5 800 ÷ 11 600 |
Droplet entrainment |
% |
≤0,01 |
Pressure in water distribution system |
ÌCE |
3-5 |
Standard of thermal calculation |
|
CTI ATC 105 |
Cooling tower construction |
Type of the cooling tower |
|
contra-flow exhaust |
Number of sections |
pcs |
1 |
Arrangement of sections |
|
liner |
Dimensions of cooling tower (width, length) |
m |
8,1õ8,0 |
Total height of cooling tower |
m |
6,90 |
Height of water distribution system |
m |
3,58 |
Height of air inlet windows |
m |
1,69 |
Height of diffuser |
m |
0,60 |
Number of clamping shoulders of water inlet, Dó |
mm |
2x300 |
Irrigation area |
m2 |
64 |
Fan installation |
Number of fans |
pcs. |
1 |
Brand of electromotor |
|
ÀÑÂÎ5Ê |
Type of connection between motor and fan |
|
Direct drive |
Fan diameter |
mm |
4500 |
Material for blades |
|
fiberglass |
Rotation rate |
rpm |
485 |
Noise level (10 meters from cooling tower) |
dB |
Not more than 70 |
Parameters of electromotor |
V/Hz/F |
380/50/3 |
Nominal power of electromotor |
kW |
37 (55) |
Electromotor protection |
|
IP55 |
Insulation class |
|
F |
t* - the air temperature according to air wet bulb thermometer
The frame of block cooling tower is made of metal framework, mounted at the installation site. All metal frameworks of the tower are treated with special high efficient anti-corrosion coating. The cooling tower is installed on a pre-prepared pool or attached to already existing one. The installation of cooling tower group consisting of 2-3 pieces is possible. The time of installation of the cooling tower 2ÁÂÃ-42 on the prepared pool is 15 ÷ 20 days.
The covering of the cooling tower consists of profiled sheets made of reinforced fiberglass polyester.
Polymer irrigator provides high water cooling effect at low aerodynamic resistance, cannot be contaminated, resistant to low air temperatures.
The fan installation is situated at the top part of block cooling tower. The fan installation consists of a frequency-driven electromotor, an impeller with plastic blades and fiberglass diffuser.
At the request of the Customer, the cooling tower is equipped with control and monitor system, which allows to:
- maintain technological mode of water cooling in the cooling towers in accordance with climatic conditions and in this way achieve a substantial saving of electricity;
- perform start-up of motors in mode, which is moderate for them and starting equipment, and in this way increase their reliability;
- to switch the motor on a lower rotational speed instead of turning off, which leads to lower maintenance costs and increases the reliability of the motors;
- to ensure complete protection of fan installation from excessive vibration in case of crippling of the diffuser and the impeller, icing of diffuser and the impeller, etc.
The tower in ready-to-operate unassembled (separate mounting units) form by road transport.